Write to
WhatsApp
Catalog

TKD Kabel TKF INDUCOM RE-2XStYSWBY-fl PiMf Data Cable

For comparison
To favorites
Vendor code:200022923
TKD Kabel TKF INDUCOM RE-2XStYSWBY-fl PiMf Data Cable
Brand
Pre-order
$19
11
Delivery across Russia
On-line payment on the website
Discount system
Purchase returns
Description
Features
Reviews

Cable TKF INDUCOM RE-2X(St)YSWBY-fl PiMf productions TKD kabel (TKD cable) It is designed to transmit data and signals in analog or digital form for measuring equipment, controllers or computer systems. It has a reinforced solid structure, has a high level of protection from interference and low attenuation. It is suitable for use in intrinsically safe installations for the 1st and 2nd explosive zone of Group II, according to IEC 60079-14 standard. It is shielded by two levels of protection: individual for each twisted pair and common screens. And also additionally protected by solid armor made of steel braid.

It can be used not only indoors, but also for laying outdoors and underground, it is resistant to chemicals of various kinds (acids, alkalis, oils), the influence of ultraviolet rays, and is immune to moisture content.

Technical specifications of the TKF INDUCOM RE-2X(St) data cableYSWBY-fl PiMf:

Number of conductive cores: up to 48;
Core cross-section: up to 1.3 mm2;
Conductor: copper, 7-wire;
Configuration: Class 2, according to DIN VDE 0295 and IEC 60228;
Marking of veins: in a pair of one color black or white with numbering;
Twisting: in layers;
Insulation material: cross-linked polyethylene (XLPE connection type);
Screen: for each pair, an individual metal film (PiMf) with a tinned copper drainage wire, a common screen is located on top, the material is laminated aluminum film (thickness 24 microns) with a tinned copper drainage wire;
Inner shell: polyvinyl chloride
Protective shield: steel braid armor (galvanized), located between PVC sheaths;
Outer shell: polyvinyl chloride;
Operating voltage: 0.3kV;
Test voltage: up to 2 kV;
Conductor resistance: 14.2 - 36.7 ohms/km depending on the cross-sectional area;
Insulation resistance: 5 GOm;
Capacity: up to 115 nF/km;
Minimum bending radius (stationary): 10 x Diameter;
Temperature (stationary): -40 ° C /+70 °C;
Temperature (movable): -5 ° C /+50 °C;
Insulation material properties: does not contribute to the spread of fire, according to IEC 60332-1-2 and IEC 60332-3-24 (Category C);
Environmental requirements: oil-resistant, resistant to aggressive chemicals (acids, alkalis, oils), UV radiation, unlimited outdoor and indoor operation.
Features
Brand
No reviews yet — yours could be the first.
All reviews 0
overall rating
Similar products
Список отзывов пуст