Cable TKF INDUCOM RE-2X(St)Yv-fl PiMf productions TKD kabel (TKD cable) It is designed to transmit data and signals in analog or digital form for measuring equipment, controllers or computer systems. It has a reinforced solid structure, has a high level of protection from interference and low attenuation. It is suitable for use in intrinsically safe installations for the 1st and 2nd explosive zone of Group II, according to IEC 60079-14 standard. It is shielded by two levels of protection: individual for each twisted pair and common screens.
It can be used not only indoors, but also outdoors, it is resistant to chemicals of various kinds (acids, alkalis, oils), the influence of ultraviolet rays, and is immune to moisture content in the air. The lines are carried out underground in accordance with the requirements of building codes.
Technical specifications of the TKF INDUCOM RE-2X(St)Yv-fl PiMf data cable:
Number of conductive cores: up to 48;Core cross-section: up to 1.3 mm2;
Conductor: copper, 7-wire;
Configuration: Class 2, according to DIN VDE 0295 and IEC 60228;
Vein marking: for pairs, one color is black or white with numbering, for triads, three colors are used - red, black and white with numbering;
Twisting: in layers;
Insulation material: cross-linked polyethylene (XLPE connection type);
Screen: for each pair, an individual metal film (PiMf) with a tinned copper drainage wire, a common screen is located on top, the material is laminated aluminum film (thickness 24 microns) with a tinned copper drainage wire;
Outer shell: polyvinyl chloride;
Operating voltage: 0.3kV;
Test voltage: up to 2 kV;
Conductor resistance: 14.2 - 36.7 ohms/km depending on the cross-sectional area;
Insulation resistance: 5 GOm;
Capacity: up to 115 nF/km;
Minimum bending radius (stationary): 7.5 x diameter;
Temperature (stationary): -40 ° C /+70 °C;
Temperature (movable): -5 ° C /+50 °C;
Insulation material properties: does not contribute to the spread of fire, according to IEC 60332-1-2 and IEC 60332-3-24 (Category C);
Environmental requirements: oil-resistant, resistant to aggressive chemicals (acids, alkalis, oils), UV radiation, unlimited outdoor and indoor operation.