Write to
WhatsApp
Catalog

Контактор 3п 300A 380В AC3 24VAC 50Гц (LC1E300B5)

For comparison
To favorites
Vendor code:LC1E300B5
-100%
Контактор 3п 300A 380В AC3 24VAC 50Гц (LC1E300B5)
Brand
Pre-order
$0$3.87
11
Related files
Delivery across Russia
On-line payment on the website
Discount system
Purchase returns
Description
Features
Reviews

Main Features

range EasyPact
Product name EasyPact TVS
the type of device or its accessories Contactor
short name of the device LC1E
contactor application Electric motor control
Active load
Application category AC-1
AC-3
description of the poles 3P
configuration of the main contacts 3 N.O.
[Ue] rated operating voltage <= 690 V переменный ток 50/60 Гц для силовая цепь
[Icw] rated short-term permissible current 300 A (<= 55 °C) переменный ток AC-3 для силовая цепь <= 440 V
320 A (<= 40 °C) переменный ток AC-1 для силовая цепь <= 440 V
engine power, kW 90 kW at 220...230 V AC 50/60 Hz AC-3
160 kW to 380 kW...400 V alternating current 50/60 Hz AC-3
160 kW at 415 V AC 50/60 Hz AC-3
185 kW at 440 V AC 50/60 Hz AC-3
200 kW to 500 V AC 50/60 Hz AC-3
250 kW at 660...690 V AC 50/60 Hz AC-3
type of control circuit Per. Current 50 Hz
control circuit voltage 24 V lane . Current 50 Hz
height 206 mm
width 213 mm
depth 219 mm
Product weight 8.5 kg

Additional features

[Up] rated pulse withstand voltage 8 test1 (coil is not connected to the power circuit) IEC 60947
[Ui] rated insulation voltage 690 V in accordance with IEC 60947-4-1
Overvoltage category III
Rated switching capacity of Irms 3000 A - 440 V AC for power circuit- in accordance with IEC 60947-4-1
rated breaking capacity 2400 A to 440 V for power circuit according to IEC 60947
[Icw] rated short-term sustained current 2200 A V <= 40 °C - 10 с для силовая цепь
the corresponding fuse rating 10 A gG <= 690 V тип 1 цепь управления IEC 60947-5-1
500 A gG <= 690 V тип 1 силовая цепь
average total resistance 0.3mOhm V 50 Hz Ith 320 A for Power circuit-
power dissipated by one pole 31 W AC-1
AC-3
voltage limits of the control circuit 0.35...0.55 Uc in <= 55 °C отпускание 50 Hz
0.85...1.1 Uc in <= 55 °C находится в состоянии работы 50 Hz
Response time 40...65 ms at short circuit
100...170 ms when opening
mechanical wear resistance 5000000 cycles
Operating frequency 1200 cycle/h in <= 55 °C
power consumption when triggered 650 V·A at 20 °C (0.9) 60 Hz
650 V·A at 20 °C (0.9) 50 Hz
power consumption during holding, V·A 10 V·A at 20 °C (0.9) 60 Hz
10 V·A at 20 °C (0.9) 50 Hz
heat transfer 8W for control circuit-
minimum switching current 5 mA control circuit
minimum switching voltage 17 Into the control circuit
time without overlap 1.5 мс при подаче напряжения guaranteed between NC and NO contact
1.5 мс при снятии напряжения guaranteed between NC and NO contact
insulation resistance > 10 mOhm control circuit
electrical wear resistance 500000 AC-3 cycles
AC-1
mounting support Panel mounting
accessions Power circuit : cable with a tip of 2,240 mm
Power chain : tires - 2 5 x 30 mm
Control circuit : screw clamp - 1 flexible cable(s) 1...4 mm2 without tip
Control circuit : screw clamp - 2 flexible cable(s) 1...4 mm2 without tip
Control circuit : screw clamp - 2 flexible cable(s) 1...2.5 mm2 with cable tip
Control circuit : screw clamp - 1 hard cable cable(s) 1...4 mm2 without tip
Control circuit : screw clamp - 2 hard cable cable(s) 1...4 mm2 without tip
Control circuit : screw clamp - 1 flexible cable(s) 1...2.5 mm2 with cable tip
tightening torque 1.2 N-m for the control circuit-
35 N-m for power circuit-

Operating conditions

standards IEC 60947-1
IEC 60947-4-1
IEC 60947-5-1
Product certification EAC
degree of IP protection IP2x in accordance with IEC 60529
protective design TH IEC 60068 3
degree of contamination 3
Ambient operating temperature -5...55 °C
ambient temperature during storage -60...80 °C
permissible air temperature around the device -20...70 °C at Uc
working height 3000 m without deterioration of nominal values
Fire resistance 850 °C IEC 60695-2-1
mechanical resistance Vibration contactor is open 1.5 g (nom.), 5...300 Hz
Shocks The contactor is closed 7 g (nom.) for 11 ms
Vibration contactor is closed 3 g (nom.), 5...300 Hz
Shocks The contactor is open 6 g (nom.) for 11 ms

Features
Brand
No reviews yet — yours could be the first.
All reviews 0
overall rating
Список отзывов пуст