Description
Features
Reviews
Main Features
range | Acti 9 | |
---|---|---|
Product name | Acti 9 iCT | |
the type of device or its accessories | Contactor | |
short name of the device | ICT | |
Scope of application | Heating-low inductive load | |
description of the poles | 2P | |
[Icw] rated short-term permissible current | 100 A AC-7A | |
configuration of the main contacts | 2 N.O. | |
network type | Alternating current | |
Application category | AC-1 according to IEC 60947-4-1 AC-7A according to UTE C 61-481 AC-1 according to EN 60947-4-1 AC-7A in accordance with EN 61095 AC-7A in accordance with IEC 61095 |
|
management method | Remote control | |
control circuit voltage | 220...240 V lane Current 50 Hz |
Additional features
network frequency | 50 Hz | |
---|---|---|
[Ue] rated operating voltage | 250 V alternating current 50 Hz | |
Maximum power | AC-7A : 2.1 W 250 V alternating current 50/60 Hz | |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz | |
[Up] rated pulse withstand voltage | 4 kV | |
type of control signal | Nerperyvnaya | |
switching frequency | 100 switches/day | |
local indication | Action indicator | |
power consumption during holding, VA | 6.5 V·A | |
power consumption when triggered | 53 In·A | |
switch design | Latched | |
mounting support | 35 mm symmetrical DIN rail | |
9 mm pitch | 6 | |
height | 85 mm | |
width | 54 mm | |
depth | 60 mm | |
colour | White | |
accessions | Control circuit : 2 1.5 mm2 tunnel type terminals for hard cable(s) Control circuit : 1 tunnel type terminals 1.5...2.5 mm2 for hard cable(s) Control circuit : 2 terminals of tunnel type 1.5...2.5 mm2 for flexible cable(s) Power circuit : 1 tunnel type terminals 6...35 mm2 for rigid or flexible cable(s) |
|
tightening torque | Power circuit- : 3.5 N-m Control circuit : 0.8 N-m A1/A2 |
|
Product compatibility | IACTc IACTp IACTs Jat |
Operating conditions
standards | EN 61095 IEC 61095 UTE C 61-481 |
|
---|---|---|
noise level | 30 dB | |
heat transfer | 2.1 W at 50/60 Hz | |
degree of IP protection | IP40 (in modular cabinet) according to IEC 60529 IP20 according to IEC 60529 |
|
degree of contamination | 2 | |
preparing for work in tropical conditions | 2 in accordance with EN 60947-4-1 | |
relative humidity | 95 % (55 °C) | |
working height | 2000 m | |
Ambient operating temperature | -5...60 °C | |
ambient temperature during storage | -40...70 °C |
Features
Brand
Schneider
No reviews yet — yours could be the first.
All reviews 0
Список отзывов пуст