Soft starter Fairford SGY-203 (90 kW; 160A)
The Fairford Electronics Synergy series soft starter is designed to start standard three-phase asynchronous motors up to 90 kW (120 hp) at 160 A when connected in line or up to 132 kW (176 hp) at 230 A when connected inside Delta (both nominal values depend on the application).
When connected to the line; designed for engines and class rating:
- 90 kW, 160 A at 400 V - shutdown class 10 (continuous)
- 75 kW, 132 A at 400 V - shutdown class 20 (continuous)
- 55 kW, 100 A at 400 V - shutdown class 30 (continuous)
When connected inside Delta; designed to match engines and shutdown classes: - Note. Power saving is not available in this mode.
- 150 kW, 277 A at 400 V - shutdown class 10 (continuous)
- 110 kW, 229 A at 400 V - shutdown class 20 (continuous)
- 90 kW, 173 A at 400 V - shutdown class 30 (continuous)
(See the Quick Start Guide and Trip Class Guide for guidance, as well as for UL current and HP ratings)
Size 2: width 143 mm, depth 232 mm, height 318 mm. IP00 (option IP20 /NEMA1 - see Related products below).
Weight: 6.5 kg.
Features include:
- Built-in keyboard
- 1 analog input + 1 analog output at 0-10 V 10 mA /4-20 mA
- 4 programmable output relays (2 groups)
- 3 x Programmable digital inputs (2 groups at 24 VDC or 110 VAC or 230 VAC + voltage dependent on 10% -15% voltage applied to terminals D1-2 Com)
- USB terminal for data logging and setting/saving parameters.
- Thermistor input (PTC).
- Input voltage: from 200 V to 480 V, at 45-65 Hz
- Recommended fuses can be found in the quick start guide
- Additional power options: Requires single-phase 110 V or 230 V AC, or 24 V DC
Cabin mount.
- Ventilation space above and below: 100 mm
- Ventilation space on the sides: 40 mm
- Ventilation space in front: 25 mm
- Mounting with 4 bolts at the rear on 80 mm x 304 mm centers.
- Rated at 50 degrees Celsius.
Manufacturer's designation: SGY-203-4-01
SYNERGY – digital softstarters with a built-in 3.5" touch control panel.
- For induction motors 380/660 V 50 Hz with rated current from 17 to 195 A.
- Built-in bypass contactor.
- Optimization of energy consumption, automatic parameter setting, programming, monitoring of operation parameters.
- USB port for reading/downloading parameters.
- The Modbus protocol is built-in. Profibus, CAN, DeviceNet is an option. IP20.
- Power supply of control circuits=24V or ~220 V.
- Full protection of the electric motor with memory.
- Power range 7.5 – 110 kW