Main Features
range | Pragma | |
---|---|---|
the type of device or its accessories | Wardrobe | |
cabinet type | The distribution cabinet | |
width | 550 mm | |
height | 900 mm | |
depth | 173 mm | |
The number of modules is 18 mm in a row | 24 | |
number of horizontal rows | 5 | |
electrical insulation class | Class II Double insulation |
|
The equipment is included | Marking Kit ( 1 ) Terminal block ( 2 ) Label with the designation ( 1 ) False closing panel ( 1 ) |
|
type of front cover | According to the customer's requirements Transparent |
Additional features
installation of the cabinet | Surface | |
---|---|---|
9 mm pitch | 48 | |
The total number of modules is 18 mm each | 120 | |
power dissipation, W | 94 Watts | |
[In] rated current | 160 A | |
type of rail | Multifix | |
cable entry | Cable or tube Cutout boards Removable boards Busbar |
|
number of terminal blocks | 1 Ground Terminal block with 32 Quick outgoing lines 1 Neutral terminal block with 35 Quick outgoing lines |
|
outgoing lines of the distribution unit | 1 x 50 mm2 for ground 1 x 50 mm2 for neutral 28 x 6 mm2 for ground 28 x 6 mm2 for neutral 3 x 25 mm2 for ground 6 x 25 mm2 for neutral |
|
cabinet material | Back part : technical plastic Front panel : technical plastic Back part : metal Front panel : metal |
|
colour | Cabinet : white ( RAL 9016 ) Door : transparent Front panel : grey ( RAL 7004 ) |
|
market segment | Housing market Small commercial enterprises |
Operating conditions
Fire resistance | Rear part : 650 °C in accordance with IEC 60695-2-1 Front panel : 650 °C according to IEC 60695-2-1 |
|
---|---|---|
degree of IP protection | IP30 without door in accordance with EN/IEC 60529 IP40 with door according to EN/IEC 60529 |
|
degree of protection IK | IK08 without door in accordance with EN/IEC 62262 IK09 with door in accordance with EN/IEC 62262 |
|
Overvoltage category | II | |
Ambient operating temperature | -25...60 °C | |
standards | EN 60439-3 EN 60695-2-11 IEC 60439-3 IEC 60529 IEC 60695-2-11 IEC 60947-7-1 IEC 62262 |
Equipment warranty
Period | The warranty period for this equipment is 18 months from the date of its commissioning, which is confirmed by the relevant document, but not more than 24 months from the date of delivery |
---|