product series | Modicon Quantum Automation Platform | |
---|---|---|
the type of device or its accessories | Digital output module with relay outputs | |
number of digital outputs | 8 |
Additional features
type of contacts | 1 N.O./N.Z. | |
---|---|---|
contact form | Form C | |
digital output voltage | 20...250 V DC 30...150 VDC 5...30 In the post. current |
|
addressing requirement | 0.5 output word | |
max. Load current | 100 mA 30...50 V post. current L/R=10 ms 2 A 250/30 V lane/post. Tungsten current 1/4 hp cos phi=0.4 3 A 250/30 V lane/post. current 300 mA 30...50 V post. Current resistive 5 A 250/30 V lane/post. Resistive currents at 60 °C |
|
current surge | <= 20 А для 10 мс емкостной | |
switching frequency | 30 Hz resistive F=0.5/I2L inductively. |
|
switching capacity, V·A | 1250 V·A resistive | |
????? ??????? ?? ?????????? ????? | <= 10 мс во время перехода 0 - 1 <= 20 мс во время перехода 1- 0 |
|
mechanical wear resistance | 10000000 cycles | |
electrical wear resistance | 100000 cycles 100 mA 30...150 V post. current L/R=10 ms 100,000 cycles 30...150 V post. Current intermediate relay 100000 cycles 300 mA 30...150 V post. Current resistive 100000 cycles 5 A 30 V post. Current resistive 200000 cycles 5 A 250 V trans. Current resistive 50000 cycles 500 mA 30...150 V post. Current resistive |
|
output overvoltage protection | Built-in, varistor, 275 V | |
interchange between channels | 1780 In action. for 1 min. 2500 Per post. current |
|
isolation between channels and bus | 1780 In action. for 1 min. 2500 V post. current for 1 min. |
|
power dissipation | 2.75 W + (0.5 x number of activated channels) | |
marking | THIS | |
local indication | 1 LED green data is exchanged over the bus (Active) 1 LED red External fault detected (F) 8 LEDs green input status |
|
rated bus current | 560 mA | |
module format | Standard | |
Product weight | 0.3 kg |
Operating conditions
Product certification | ABS C-Tick DNV FM Class 1 section 2 GL GOST RINA RMRS |
|
---|---|---|
standards | CSA C22,2 No 142 UL 508 |
|
resistance to electrostatic discharge | 4 kV contact according to IEC 801-2 8 kV in the air in accordance with IEC 801-2 |
|
resistance to electromagnetic fields | 10 V/m 80...2000 MHz in accordance with IEC 801-3 | |
Ambient operating temperature | 0...60 °C | |
ambient temperature during storage | -40...85 °C | |
relative humidity | 95 % non-condensing | |
working height | <= 5000 м |