Main Features
product series | EasyPact | |
---|---|---|
the type of device or its accessories | Automatic switch | |
short name of the device | Easypact EZC630N | |
Name of the circuit breaker | Easypact EZC630N | |
Scope of application | Distribution | |
description of the poles | 3P | |
description of the protected poles | 3t | |
network type | Alternating current Direct current |
|
network frequency | 50/60 Hz | |
[In] rated current | 630 A ( 40 °C ) | |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz according to IEC 60947-2 | |
[Up] rated pulse withstand voltage | 6 kV in accordance with IEC 60947-2 | |
[Ue] rated operating voltage | 250 V direct current according to IEC 60947-2 440 V alternating current 50/60 Hz in accordance with IEC 60947-2 |
|
breaking capacity code | N | |
breaking capacity | ICU 40 kA 220/230 V AC 50/60 Hz according to IEC 60947-2 ICU 36 kA V 400/415 V AC 50/60 Hz according to IEC 60947-2 ICU 36 kA in 380 V AC 50/60 Hz according to IEC 60947-2 ICU 36 kA in 440 V alternating current 50/60 Hz in accordance with IEC 60947-2 |
|
[Ics] rated operating breaking capacity | Ics 40 kA 220/230 V AC 50/60 Hz conforming to IEC 60947-2 Ics 36 kA 380 V AC 50/60 Hz conforming to IEC 60947-2 Ics 36 kA 400/415 V AC 50/60 Hz conforming to IEC 60947-2 ICS 18 kA 440 V alternating current 50/60 Hz in accordance with IEC 60947-2 |
|
compliance with insulation requirements | Yes in accordance with IEC 60947-2 | |
Application category | Category A | |
name of the control unit | TM-D | |
technology of the control and management unit | Thermomagnetic | |
rated current of the decoupler | 500 A ( 50 °C ) | |
types of implemented protections | Overload protection Short circuit protection |
|
degree of contamination | 3 in accordance with IEC 60947 |
Additional features
management method | Toggle switch | |
---|---|---|
switch design | Stationary | |
mounting support | Rear mounting plate | |
connection from the upper side | The front one | |
connection from the bottom side | The front one | |
mechanical wear resistance | 10000 cycles | |
electrical wear resistance | Category A : 3000 cycles 415 V AC 50/60 Hz according to IEC 60947-2 | |
connection step | 45 mm | |
local indication | Direct indication of the contact position | |
contact position indicator | Yes | |
the operating current of the electromagnetic release | 5000 A | |
installing neutral protection | Without protection | |
protection setpoint with a long delay in the operation of the Ir | Fixed | |
the type of adjustment of the overload response time delay | Fixed | |
earth fault protection | Without | |
height | 255 mm | |
width | 185 mm | |
depth | 140 mm | |
Product weight | 6.4 kg | |
quantity in one set | 1 piece | |
colour | Black |
Operating conditions
standards | EN/IEC 60947-1 EN/IEC 60947-2 JIS C8201-2-2 GB/T 14048.2 |
|
---|---|---|
degree of IP protection | IP20 according to IEC 60529 | |
degree of protection IK | IK07 in accordance with EN 50102 | |
Ambient operating temperature | -25...70 °C | |
ambient temperature during storage | -35...85 °C |