Description
Features
Reviews
Main Features
product series | Easypact CVS400...630 | |
---|---|---|
the type of device or its accessories | Automatic switch | |
short name of the device | CVS630F | |
Scope of application | Distribution | |
description of the poles | 3P | |
description of the protected poles | 3d | |
earth fault protection | Without | |
[In] rated current | 630 A ( 40 °C ) | |
breaking capacity code | F | |
network type | Alternating current | |
breaking capacity | 36 kA Icu according to IEC 60947-2 V 380/415 V AC 50/60 Hz 30 kA Icu according to IEC 60947-2 V 440 V AC 50/60 Hz 40 kA Icu according to IEC 60947-2 V 220/240 V AC 50/60 Hz |
|
Application category | Category A | |
local indication | LED "105 % Ir" LED "90% Ir" The LED is "ready to work" |
|
name of the control unit | ETS 2.3 | |
technology of the control and management unit | Electronic | |
rated current of the decoupler | 630 A ( 40 °C ) | |
types of implemented protections | Instant short circuit protection Overload protection (with long time delay) Short circuit protection with short time delay |
Additional features
network frequency | 50/60 Hz | |
---|---|---|
management method | Toggle switch | |
switch design | Stationary | |
mounting support | Rear mounting plate | |
connection from the upper side | The front one | |
connection from the bottom side | The front one | |
accessions | Screw connection | |
[Up] rated pulse withstand voltage | 8 kV in accordance with EN/IEC 60947-2 | |
[Ics] rated operating breaking capacity | 40 kA according to IEC 60947-2 220/240 V alternating current 50/60 Hz 36 kA according to IEC 60947-2 380/415 V alternating current 50/60 Hz 23 kA according to IEC 60947-2 440 V alternating current 50/60 Hz |
|
mechanical wear resistance | 15000 cycles | |
electrical wear resistance | 4000 cycles according to IEC 60947-2 415 V In | |
connection step | 45 mm | |
contact position indicator | Yes | |
protective functions of the control unit | LSoI | |
protection setpoint with a long delay in the operation of the Ir | 6 adjustable settings | |
[Ir] overload protection trip current setpoint | 315...630 A | |
the type of adjustment of the overload response time delay | Fixed | |
[tr] adjustable overload protection time setting | 90...180 with 1.5 x Ir 3.2...5 with 7.2 x Ir 5...7.5 with 6 x Ir |
|
thermal memory | Yes | |
Isd short circuit protection setpoint range | 8 adjustable. settings | |
[Isd] short circuit actuation current setpoint | 2...10 x Ir | |
type of short circuit protection response time setting | Fixed | |
The range of instantaneous protection settings of type Ii | Fixed | |
the setpoint of the instantaneous response current | 11 x In | |
height | 255 mm | |
width | 140 mm | |
depth | 110 mm |
Operating conditions
protection class against electric shock | Class II | |
---|---|---|
standards | EN 60947-2 IEC 60947-2 |
|
Product certification | GOST IEC |
|
degree of IP protection | IP40 | |
Ambient operating temperature | -25...70 °C | |
ambient temperature during storage | -50...85 °C |
Features
Brand
Schneider
No reviews yet — yours could be the first.
All reviews 0
Список отзывов пуст