Description
Features
Reviews
Main Features
| product series | C120 | |
|---|---|---|
| range | Acti 9 | |
| Product name | C120 | |
| the type of device or its accessories | Miniature circuit breaker | |
| short name of the device | C120N | |
| Scope of application | Distribution | |
| description of the poles | 3P | |
| number of protected poles | 3 | |
| [In] rated current | 125 A at 30 °C | |
| network type | Alternating current | |
| technology of the control and management unit | Thermomagnetic | |
| curve code | D | |
| breaking capacity | 6 kA Icu according to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA Icu in accordance with EN/IEC 60947-2 - 380...415 V alternating current 50/60 Hz 20 kA Icu in accordance with EN/IEC 60947-2 - 220...240 V alternating current 50/60 Hz 10 kA Icu in accordance with EN/IEC 60947-2 - <= 375 В постоянный ток 10000 A Icn in accordance with EN/IEC 60898-1 - 230...400 V alternating current 50/60 Hz |
|
| compliance with insulation requirements | Yes in accordance with IEC 60947-2 |
Additional features
| network frequency | 50/60 Hz | |
|---|---|---|
| [Ue] rated operating voltage | <= 375 В постоянный ток 220...240 V alternating current 50/60 Hz 380...415 V alternating current 50/60 Hz 440 V alternating current 50/60 Hz 230...400 V alternating current 50/60 Hz |
|
| electromagnetic shutdown limit | 10...14 x In | |
| [Ics] rated operating breaking capacity | 4.5 kA at 75% breaking capacity according to EN/IEC 60947-2 - 440 V alternating current 50/60 Hz 7.5 kA at 75% breaking capacity in accordance with EN/IEC 60947-2 - 380...415 V alternating current 50/60 Hz 15 kA at 75% breaking capacity in accordance with EN/IEC 60947-2 - 220...240 V alternating current 50/60 Hz 7,500 A at 75% breaking capacity in accordance with EN/IEC 60898-1 - 230...400 V alternating current 50/60 Hz 10 kA at 100% breaking capacity according to EN/IEC 60947-2 - <= 375 В постоянный ток |
|
| restriction class | 3 in accordance with EN/IEC 60947-2 | |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz according to EN/IEC 60947-2 | |
| [Up] rated pulse withstand voltage | 6 kV in accordance with EN/IEC 60947-2 | |
| contact position indicator | Yes | |
| management method | Toggle switch | |
| local indication | ON/OFF display | |
| switch design | Latched | |
| mounting support | 35 mm symmetrical DIN rail | |
| compatibility of the distribution unit with comb tires | No | |
| 9 mm pitch | 9 | |
| height | 81 mm | |
| width | 81 mm | |
| depth | 73 mm | |
| Product weight | 0.615 kg | |
| colour | White | |
| mechanical wear resistance | 20000 cycles | |
| electrical wear resistance | 5000 cycles according to IEC 60947-2 | |
| accessions | Tunnel type terminals 1.5...35 mm2 flexible Tunnel type terminals 1...50 mm2 hard |
|
| wire stripper length | 15 mm | |
| tightening torque | 3.5 N-m | |
| earth fault protection | A separate block |
Operating conditions
| standards | EN/IEC 60947-2 EN/IEC 60898-1 |
|
|---|---|---|
| Product certification | EAC | |
| degree of IP protection | IP20 according to IEC 60529 | |
| degree of contamination | 3 in accordance with IEC 60947-2 | |
| Overvoltage category | IV | |
| preparing for work in tropical conditions | 2 in accordance with IEC 60068-1 | |
| relative humidity | 95 % 55 °C | |
| working height | 2000 m | |
| Ambient operating temperature | -25...70 °C | |
| ambient temperature during storage | -40...85 °C |
Features
Brand
Schneider
No reviews yet — yours could be the first.
All reviews 0
Список отзывов пуст