Description
Features
Reviews
Main Features
product series | OsiSense ATEX D | |
---|---|---|
The name of the series | Standard format | |
the type of device or its accessories | Limit switch | |
special application area of the product | For applications related to the movement of goods | |
short name of the device | XCKMR | |
housing type | Fixed | |
type of head | Rotary head | |
material | Metal | |
montage | The body | |
movement of the working head | Rotary | |
handle type | Metal cross arm with fixation, square pin 6 mm, L=200 mm | |
activating the switch | Any movable part | |
type of supply | Side feed, 2 directions | |
electrical connection | Screw clamps, 1 x 0.34...2 x 1.5 mm2 | |
number of cable entries | 2 threaded cable gland (M20 x 1.5) for cable gland 1 threaded cable gland (M20 x 1.5) for Cable gland (included), cable outer diameter: 7...13 mm |
|
number of poles | 4 | |
type of contacts | 2 x (2 N. s.) | |
contact isolation form | Eg | |
the work of contacts | Slow. open, non-overlapping. | |
number of steps | 2 | |
??????? ?????????? ??????????? (???? ??????????) | 1 for each direction | |
direct opening | With | |
min. the moment of operation | 0.5 N-m | |
max. activation speed | 1.5 m/s | |
degree of IP protection | IP66 in accordance with IEC 60529 |
Additional features
min. activation speed | 6 m/min | |
---|---|---|
max. shear angle | 180 ° -180 ° |
|
the code designation of the contact | A300, AC-15 (240 V, Ie=3 A) in accordance with EN 60947-5-1 A300, AC-15 (240 V, Ie=3 A) in accordance with IEC 60947-5-1 Appendix A Q150, DC-13 (125 V, Ie=0.55 A) in accordance with EN 60947-5-1 Q150, DC-13 (125 V, Ie=0.55 A) in accordance with IEC 60947-5-1 Appendix A |
|
[Ui] rated insulation voltage | 500 V according to NF C 20-040 group C 500 V, degree of contamination: 3 in accordance with IEC 60947-1 500 V, degree of contamination: 3 according to VDE 0110 300 V in accordance with UL 508 |
|
contact resistance of the clamps | <= 25 МОм в соответствии с МЭК 60255-7 категория 3 <= 25 МОм в соответствии с NF C 93-050 метод A |
|
[Up] rated pulse withstand voltage | 6 kV in accordance with IEC 60664 6 kV in accordance with IEC 60947-1 |
|
?????? ?? ????????? ????????? | 10 A fuse cartridge, type gG | |
mechanical wear resistance | 2000000 cycles | |
marking | II2 D-Ex TB IIIC T85 ° C Db IP66/67 | |
width | 118 mm | |
height | 77 mm | |
depth | 59 mm |
Operating conditions
Impact resistance | 50 gn in accordance with IEC 60068-2-27 | |
---|---|---|
vibration resistance | 25 gn 10...500 Hz IEC 60068-2-6 | |
protection class against electric shock. by electric current | Class I according to IEC 60536 Class I according to NF C 20-030 |
|
Ambient operating temperature | -20...60 °C | |
protective design | TC | |
dusting zone | Zone 21 - 22 | |
Product certification | INERIS 04ATEX0014X IEC-Ex INE 17.0020X |
|
standards | EN/IEC 60079-0 EN/IEC 60079-31 |
|
directives | 2014/34/EU - ATEX directive |
Features
Brand
Schneider
No reviews yet — yours could be the first.
All reviews 0