Description
Features
Reviews
Main Features
product series | Interface for discrete signals | |
---|---|---|
the type of device or its accessories | Interface module with electromechanical inputs | |
type of contacts | 1 Switching. | |
[Uc] control circuit voltage | 24 V | |
type of control circuit | Per./post. current | |
control circuit current frequency | 50/60 Hz | |
the size of the step in width | 17.5 mm | |
[In] rated current | <= 55 mA пер. ток <= 62 mA пост. ток |
|
protection against switching on with reverse polarity | With | |
?????? ?? ????????? ????????? | 16 A external fuse gF (Ik <= 2,5 кA пер. тока и Ik <= 100 A пост. тока) 16 A external fuse gG (Ik <= 2,5 кA пер. тока и Ik <= 100 A пост. тока) |
|
[Ith] conditional thermal current in the open air | 2 A in accordance with IEC 60947-1 | |
local indication | The green mechan. contact position indicator and 1 control signal status indicated by a green LED |
Additional features
voltage limits of the control circuit | 30 V supply voltage threshold: 16.5V | |
---|---|---|
body color | Gray | |
accessions | Terminal block with screw terminals | |
release voltage | <= 3.8 В | |
holding current | >=4.9 mA DC >=5.2 mA trans. current |
|
power dissipation, W | <= 1.5 Вт | |
max. switching voltage | 125 VDC 252 V alternating current |
|
[Ue] rated operating voltage | <= 125 V постоянный ток в соответствии с IEC 60947-5-1 <= 230 V переменный ток в соответствии с IEC 60947-5-1 |
|
network frequency | 50/60 Hz | |
[Icw] rated short-term permissible current | 1 A AC-13 Ue: 230 V for 1,000,000 cycles according to IEC 60947-5-1 1 A AC-14 Ue: 230 V for 1,000,000 cycles according to IEC 60947-5-1 1 A AC-15 Ue: 230 V for 1,000,000 cycles according to IEC 60947-5-1 1 A DC-13 Ue: 24 V for 1,000,000 cycles according to IEC 60947-5-1 2 A AC-12 Ue: 230 V for 1,000,000 cycles in accordance with IEC 60947-5-1 2 A DC-12 Ue: 24 V for 1,000,000 cycles in accordance with IEC 60947-5-1 |
|
minimum switching current | 3 mA | |
minimum switching voltage | 17 In | |
electrical reliability | <= 0,00000001 | |
Response time | <= 12 мс между снятием напряжения с катушки и замыканием Н.З. контакта <= 12 мс между снятием напряжения с катушки и замыканием Н.О. контакта <= 12 мс между подачей напряжения на катушку и замыканием Н.З. контакта <= 12 мс между подачей напряжения на катушку и замыканием Н.О. контакта |
|
contact rattle time | <= 3 мс | |
operating frequency, Hz | <= 6 Гц при отсутствии нагрузки <= 0.5 Гц при Ie |
|
mechanical wear resistance | >=10000000 cycles | |
[Ui] rated insulation voltage | 250 V in accordance with IEC 60947-1 250 V according to VDE 0110 group C |
|
Fire resistance | V0 in accordance with UL 94 | |
cable cross section | 0.27...4 mm2, 1 hard wire 0.34...2.5 mm2, 1 or 2 flexible wires with cable tip 0.6...2.5 mm2, 1 or 2 flexible wires without a tip 0.27...2.5 mm2, 2-wire hard |
|
working position | Any position | |
installation category | II in accordance with IEC 60947-1 | |
mounting support | Unbalanced DIN rail Combined rail Symmetrical DIN rail |
|
Product weight | 0.095 kg |
Operating conditions
resistance to short-term loss of supply voltage | 8 ms | |
---|---|---|
electrical insulation strength | 1500 V between independent contacts 2500 V between the connected interface and the ground 4000 V between coil and contact circuits |
|
standards | IEC 60947-5-1 | |
Product certification | BV CSA DNV LROS (Lloyds register of shipping) UL |
|
degree of IP protection | IP20 according to IEC 60529 | |
protective design | TC | |
Fire resistance | 850 °C in accordance with IEC 60695-2-1 | |
Impact resistance | 50 gn for 11 ms in accordance with IEC 60068-2-27 | |
vibration resistance | 6 gn (f=10...55 Hz) in accordance with IEC 60068-2-6 | |
electromagnetic compatibility | Pulse surge resistance test 1.2/50 ms, 0.25 kV for U >50 V in accordance with IEC 255-4 Pulse surge resistance test 1.2/50 ms, 0.5 kV for U >50 V in accordance with IEC 255-4 Electrolytic discharge resistance test level 3.8 kV in accordance with IEC 61000-4-2 Test for resistance to switching interference, at the input/output of 1 kV in accordance with IEC 61000-4-4 Test for resistance to switching interference, in a 2 kV power supply circuit in accordance with IEC 61000-4-4 |
|
Ambient operating temperature | -20...60 °C at Un -5...40 °C unlimited use |
|
ambient temperature during storage | -40...70 °C | |
working height | <= 3000 м | |
degree of contamination | 3 in accordance with IEC 60947-5-1 |