Description
Features
Reviews
Main Features
range | EasyPact | |
---|---|---|
Product name | EasyPact TVS | |
the type of device or its accessories | Contactor | |
short name of the device | LC1E | |
contactor application | Electric motor control Active load |
|
Application category | AC-1 AC-3 |
|
description of the poles | 3P | |
configuration of the main contacts | 3 N.O. | |
[Ue] rated operating voltage | <= 690 V переменный ток 50/60 Гц для силовая цепь | |
[Icw] rated short-term permissible current | 300 A (<= 55 °C) переменный ток AC-3 для силовая цепь <= 440 V 320 A (<= 40 °C) переменный ток AC-1 для силовая цепь <= 440 V |
|
engine power, kW | 90 kW at 220...230 V AC 50/60 Hz AC-3 160 kW to 380 kW...400 V alternating current 50/60 Hz AC-3 160 kW at 415 V AC 50/60 Hz AC-3 185 kW at 440 V AC 50/60 Hz AC-3 200 kW to 500 V AC 50/60 Hz AC-3 250 kW at 660...690 V AC 50/60 Hz AC-3 |
|
type of control circuit | Per. Current 50 Hz | |
control circuit voltage | 110 V lane Current 50 Hz | |
height | 206 mm | |
width | 213 mm | |
depth | 219 mm | |
Product weight | 8.5 kg |
Additional features
[Up] rated pulse withstand voltage | 8 test1 (coil is not connected to the power circuit) IEC 60947 | |
---|---|---|
[Ui] rated insulation voltage | 690 V in accordance with IEC 60947-4-1 | |
Overvoltage category | III | |
Rated switching capacity of Irms | 3000 A - 440 V AC for power circuit- in accordance with IEC 60947-4-1 | |
rated breaking capacity | 2400 A to 440 V for power circuit according to IEC 60947 | |
[Icw] rated short-term sustained current | 2200 A V <= 40 °C - 10 с для силовая цепь | |
the corresponding fuse rating | 10 A gG <= 690 V тип 1 цепь управления IEC 60947-5-1 500 A gG <= 690 V тип 1 силовая цепь |
|
average total resistance | 0.3mOhm V 50 Hz Ith 320 A for Power circuit- | |
power dissipated by one pole | 31 W AC-1 AC-3 |
|
voltage limits of the control circuit | 0.35...0.55 Uc in <= 55 °C отпускание 50 Hz 0.85...1.1 Uc in <= 55 °C находится в состоянии работы 50 Hz |
|
Response time | 40...65 ms at short circuit 100...170 ms when opening |
|
mechanical wear resistance | 5000000 cycles | |
Operating frequency | 1200 cycle/h in <= 55 °C | |
power consumption when triggered | 650 V·A at 20 °C (0.9) 60 Hz 650 V·A at 20 °C (0.9) 50 Hz |
|
power consumption during holding, V·A | 10 V·A at 20 °C (0.9) 60 Hz 10 V·A at 20 °C (0.9) 50 Hz |
|
heat transfer | 8W for control circuit- | |
minimum switching current | 5 mA control circuit | |
minimum switching voltage | 17 Into the control circuit | |
time without overlap | 1.5 мс при подаче напряжения guaranteed between NC and NO contact 1.5 мс при снятии напряжения guaranteed between NC and NO contact |
|
insulation resistance | > 10 mOhm control circuit | |
electrical wear resistance | 500000 AC-3 cycles AC-1 |
|
mounting support | Panel mounting | |
accessions | Power circuit : cable with a tip of 2,240 mm Power chain : tires - 2 5 x 30 mm Control circuit : screw clamp - 1 flexible cable(s) 1...4 mm2 without tip Control circuit : screw clamp - 2 flexible cable(s) 1...4 mm2 without tip Control circuit : screw clamp - 2 flexible cable(s) 1...2.5 mm2 with cable tip Control circuit : screw clamp - 1 hard cable cable(s) 1...4 mm2 without tip Control circuit : screw clamp - 2 hard cable cable(s) 1...4 mm2 without tip Control circuit : screw clamp - 1 flexible cable(s) 1...2.5 mm2 with cable tip |
|
tightening torque | 1.2 N-m for the control circuit- 35 N-m for power circuit- |
Operating conditions
standards | IEC 60947-1 IEC 60947-4-1 IEC 60947-5-1 |
|
---|---|---|
Product certification | EAC | |
degree of IP protection | IP2x in accordance with IEC 60529 | |
protective design | TH IEC 60068 3 | |
degree of contamination | 3 | |
Ambient operating temperature | -5...55 °C | |
ambient temperature during storage | -60...80 °C | |
permissible air temperature around the device | -20...70 °C at Uc | |
working height | 3000 m without deterioration of nominal values | |
Fire resistance | 850 °C IEC 60695-2-1 | |
mechanical resistance | Vibration contactor is open 1.5 g (nom.), 5...300 Hz Shocks The contactor is closed 7 g (nom.) for 11 ms Vibration contactor is closed 3 g (nom.), 5...300 Hz Shocks The contactor is open 6 g (nom.) for 11 ms |