Description
Features
Reviews
Main Features
range | TeSys | |
---|---|---|
Product name | TeSys D | |
the type of device or its accessories | Contactor | |
short name of the device | LC1D | |
contactor application | Electric motor control Active load |
|
Application category | AC-1 AC-3 AC-4 |
|
description of the poles | 3P | |
configuration of the main contacts | 3 N.O. | |
[Ue] rated operating voltage | <= 300 В постоянный ток 25...400 Hz для силовая цепь <= 1000 V переменный ток для силовая цепь |
|
[Icw] rated short-term permissible current | 125 A (<= 60 °C) в <= 440 V переменный ток AC-1 для силовая цепь 95 A (<= 60 °C) в <= 440 V переменный ток AC-3 для силовая цепь |
|
engine power, kW | 45 kW in 660...690 V AC 50/60 Hz AC-3 45 kW at 415...440 V AC 50/60 Hz AC-3 55 kW 500 V AC 50/60 Hz AC-3 45 kW at 1000 V AC 50/60 Hz AC-3 15 kW at 400 V AC 50/60 Hz AC-4 25 kW 220...230 V alternating current 50/60 Hz AC-3 45 kW in 380...400 V alternating current 50/60 Hz AC-3 |
|
engine power, hp | 20 HP 200/208 V Alternating current 50/60 Hz for 3 Phase electric motors 7.5 HP 115 V AC 50/60 Hz for 1 Phase Electric Motors 15 HP 230/240 V Alternating current 50/60 Hz for 1 phase Electric motors 25 hp 230/240 V Alternating current 50/60 Hz for 3 Phase electric motors 60 hp V 460/480 V Alternating current 50/60 Hz for 3 Phase electric motors 60 hp at 575/600 V Alternating current 50/60 Hz for 3 Phase electric motors |
|
type of control circuit | Post. Current wide range | |
control circuit voltage | 12 V post. current | |
vspom. contacts available on each contactor | 1 N.O. + 1 N.Z. | |
[Up] rated pulse withstand voltage | In accordance with IEC 60947 | |
Overvoltage category | III | |
[Ith] conditional thermal current in the open air | 125 A in <= 60 °C для силовая цепь 10 A in <= 60 °C для цепь сигнализации |
|
Rated switching capacity of Irms | 1100 A to 440 V for power circuit according to IEC 60947 140 A alternating current for alarm circuit according to IEC 60947-5-1 250 A direct current for alarm circuit according to IEC 60947-5-1 |
|
rated breaking capacity | 1100 A to 440 V for power circuit according to IEC 60947 | |
[Icw] rated short-term sustained current | 1100 A <= 40 °C 1 с силовая цепь 135 A <= 40 °C 10 мин силовая цепь 400 A <= 40 °C 1 мин силовая цепь 800 A <= 40 °C 10 с силовая цепь 100 A 1 s alarm circuit 120 A 500 ms alarm circuit 140 A 100 ms alarm circuit |
|
the corresponding fuse rating | 160 A gG in <= 690 V координация тип 2 для силовая цепь 200 A gG in <= 690 V координация тип 1 для силовая цепь 10 A gG for alarm circuit according to IEC 60947-5-1 |
|
average total resistance | 0.8mOhm V 50 Hz - Ith 125 A for power circuit | |
[Ui] rated insulation voltage | 1000 V for power circuit according to IEC 60947-4-1 600 V for CSA certification power circuit 600 V for UL certification power circuit 690 V for alarm circuit according to IEC 60947-1 600 V for CSA certification alarm circuit 600 V for UL certification alarm circuit |
|
electrical wear resistance | 1.2 million cycles of 95 A AC-3 at Ue <= 440 V 1.3 million cycles 125 A AC-1 at Ue <= 440 V |
|
power dissipated by one pole | 7.2W AC-3 12.5W AC-1 |
|
protective cover | With | |
mounting support | Panel mounting The rail |
|
standards | CSA C22.2 № 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
|
Product certification | BV CCC DNV GL GOST LROS (Lloyds register of shipping) RINA |
|
accessions | Control circuit : screw clamp 2 cable(s) 1...2.5 mm2 - cable stiffness: flexible - with cable tip Control circuit : screw clamp 1 cable(s) 1...4 mm2 - cable stiffness: flexible - without cable tip Control circuit : screw clamp 2 cable(s) 1...4 mm2 - cable stiffness: flexible - without cable tip Control circuit : screw clamp 1 cable(s) 1...4 mm2 - cable stiffness: rigid cable - without cable tip Control circuit : screw clamp 2 cable(s) 1...4 mm2 - cable stiffness: rigid cable - without cable tip Control circuit : screw clamp 1 cable(s) 1...2.5 mm2 - cable stiffness: flexible - with cable tip Power circuit : connector 1 cable(s) 4...50 mm2 - cable stiffness: flexible - without cable tip Power circuit : connector 2 cable(s) 4...25 mm2 - cable stiffness: flexible - without cable tip Power circuit : connector 1 cable(s) 4...50 mm2 - Cable stiffness: flexible - with cable tip Power circuit : connector 2 cable(s) 4...16 mm2 - Cable stiffness: flexible - with cable tip Power circuit : connector 1 cable(s) 4...50 mm2 - cable stiffness: rigid cable - without cable tip Power circuit : connector 2 cable(s) 4...25 mm2 - cable stiffness: rigid cable - without cable tip |
|
tightening torque | Power circuit : 9 Nm - connector - flat with a screwdriver. Ø 6 - Ø 8 mm Power circuit : 9 Nm - 4 mm hex socket Control circuit : 1.2 N-m - screw clamp - flat with a screwdriver. Ø 6 mm Control circuit : 1.2 N-m - screw clamp - using a Philips No. 2 screwdriver |
|
Response time | 20...35 ms shutdown 95...130 ms switching on |
|
a safe level of reliability | B10d=1369863 cycles contactor with rated load according to EN/ISO 13849-1 B10d=20000000 cycles contactor with mechanical load according to EN/ISO 13849-1 |
|
mechanical wear resistance | 10 million cycles | |
Operating frequency | 3600 cycle/h in <= 60 °C |
Additional features
the technology of using coils | Without built-in overload protection module | |
---|---|---|
voltage limits of the control circuit | 0.75...1.2 Uc is in operation at 55 °C, direct current 0.1...0.3 Uc release at 55 °C, direct current |
|
the time constant | 75 ms | |
starting power, W | 22 W at 20 °C | |
power consumption when holding, W | 22 W at 20 °C | |
the type of vspom. contacts | Type mechanically coupled (1 N.O. + 1 N.Z.) in accordance with IEC 60947-5-1 Type duplicate contact (1 N.Z.) in accordance with IEC 60947-4-1 |
|
alarm circuit frequency | 25...400 Hz | |
minimum switching current | 5 mA for alarm circuit | |
minimum switching voltage | 17 V for alarm circuit | |
time without overlap | 1.5 ms when voltage is removed (between NC and NO contact) 1.5 ms when voltage is applied (between NC and NO contact) |
|
insulation resistance | > 10 mOhm for alarm circuit |
Operating conditions
degree of IP protection | IP20 front panel in accordance with IEC 60529 | |
---|---|---|
protective design | TH in accordance with IEC 60068-2-30 | |
degree of contamination | 3 | |
Ambient operating temperature | -5...60 °C | |
ambient temperature during storage | -60...80 °C | |
permissible air temperature around the device | -40...70 °C at Uc | |
working height | 3000 m without temperature degradation | |
Fire resistance | 850 °C in accordance with IEC 60695-2-1 | |
Fire resistance | V1 in accordance with UL 94 | |
mechanical resistance | Vibration contactor is open 2 g (nom.), 5...300 Hz Shocks The contactor is open 8 g (nom.) for 11 ms Vibration contactor is closed 3 g (nom.), 5...300 Hz Shocks The contactor is closed 10 gn for 11 ms |
|
height | 127 mm | |
width | 85 mm | |
depth | 186 mm | |
Product weight | 2.61 kg |
Features
Brand
Schneider
No reviews yet — yours could be the first.
All reviews 0
Список отзывов пуст