Frequency converters VLT HVAC Drive FC 102 designed specifically for the efficient operation of pumps, compressors and fans. All the necessary algorithms and tools are built into their software block for the successful management of technological processes specific to this field of application. Maximum optimization of energy consumption saves drive resources and provides economic benefits of operation.
Extensive possibilities for flexible equipment configuration, modern software support and a user-friendly interface for maintenance. Thanks to the built-in intelligent control, for most cases, a PLC is not required at all. The modular architecture allows you to upgrade the system if necessary, a large selection of optional units and accessories. For the harshest conditions, protection versions are available up to the level with fully sealed enclosures.
A huge range of power variations, a range of applications from low to ultra-high power values, several types of low-voltage power ratings in the range of 200 - 690 V. All models have built-in DC chokes and anti-interference filters.
Technical characteristics of Danfoss VLT AQUA Drive FC 202 electric drives
- Supply voltage: 3AC 200-240V, 380 - 480V, 525 - 600V, 525-690V;
- Electric motor power: 1.1- 1400 kW;
- Output current: 2.1 - 1720 A;
- Management methods: scalar, vector (touch and sensorless), magnetic flux vector control;
- Output frequency: 0 - 590 Hz;
- Permissible overloads: the normal mode is up to 110% of the nom. current for 60 seconds;
- Enclosure protection class: IP00, IP20, IP21, IP54, IP55, IP66;
- Interfaces: RS485, USB, опционально PROFIBUS, DeviceNet, AK-LonWorks, BACnet, BACnet/IP, PROFINET, EtherNet/IP, Modbus TCP;
- Visualization and customization tools: control panel with LCD display, push-button navigation, software for control and parameterization using a personal computer;
- Other features and functions: intelligent logic controller, built-in profile functions (for pumps, fans and compressors), automatic optimization of energy consumption, safe torque removal, maximum speed limitation and others.
VLT HVAC Drive FC 102 I/O Configuration
- Analog: 2 inputs and 1 output;
- Digital: 6 inputs and 2 outputs;
- relay: 2 outputs;
- connection of feedback sensors.
Optional VLT HVAC Drive FC 102 Drive Modules
- Industrial network protocol modules.
- I/O expansion board.
- Modules for connecting feedback sensors.
- Security function extension modules.
- Modules for connecting temperature sensors.
- Expansion of the motion control system.
- Backup power supply (DC 24 V).
Parameters of standard sizes of electric drives VLT HVAC Drive FC 102
supply voltage 200 - 240 V
Type of drive | Current, A | Power, kW |
FC-102P1K1T2… | 6,6 | 1,1 |
FC-102P1K5T2… | 7,5 | 1,5 |
FC-102P2K2T2… | 10,6 | 2,2 |
FC-102P3K0T2… | 12,5 | 3,0 |
FC-102P3K7T2… | 16,7 | 3,7 |
FC-102P5K5T2… | 24,2 | 5,5 |
FC-102P7K5T2… | 30,8 | 7,5 |
FC-102P11KT2… | 46,2 | 11 |
FC-102P15KT2… | 59,4 | 15 |
FC-102P18KT2… | 74,8 | 18,5 |
FC-102P22KT2… | 88,0 | 22 |
FC-102P30KT2… | 115 | 30 |
FC-102P37KT2… | 143 | 37 |
FC-102P45KT2… | 170 | 45 |
supply voltage 380 - 480 V
Type of drive | Current, A | Power, kW |
FC-102P1K1T4… | 3,0 | 1,1 |
FC-102P1K5T4… | 4,1 | 1,5 |
FC-102P2K2T4… | 5,6 | 2,2 |
FC-102P3K0T4… | 7,2 | 3,0 |
FC-102P4K0T4… | 10 | 4,0 |
FC-102P5K5T4… | 13 | 5,5 |
FC-102P4K0T4… | 16 | 7,5 |
FC-102P11KT4… | 24 | 11 |
FC-102P15KT4… | 32 | 15 |
FC-102P18KT4… | 37,5 | 18 |
FC-102P22KT4… | 44 | 22 |
FC-102P30KT4… | 61 | 30 |
FC-102P37KT4… | 73 | 37 |
FC-102P45KT4… | 90 | 45 |
FC-102P55KT4… | 106 | 55 |
FC-102P75KT4… | 147 | 75 |
FC-102P90KT4… | 177 | 90 |
supply voltage 380 - 500 V
Type of drive | Current, A | Motor power, kW | ||
norm. mode | heavy. mode | norm. mode | heavy. mode | |
FC-302N90KT5 | 110 | 90 | 212 | 177 |
FC-302N110T5 | 132 | 110 | 260 | 212 |
FC-302N132T5 | 160 | 132 | 315 | 260 |
FC-302N160T5 | 200 | 160 | 395 | 315 |
FC-302N200T5 | 250 | 200 | 480 | 395 |
FC-302N250T5 | 315 | 250 | 588 | 480 |
FC-302P250T5 | 315 | 250 | 600 | 480 |
FC-302P315T5 | 355 | 315 | 658 | 600 |
FC-302P355T5 | 400 | 355 | 745 | 658 |
FC-302P400T5 | 450 | 400 | 800 | 695 |
FC-302P450T5 | 500 | 450 | 880 | 800 |
FC-302P500T5 | 560 | 500 | 990 | 880 |
FC-302P560T5 | 630 | 560 | 1120 | 990 |
FC-302P630T5 | 710 | 630 | 1260 | 1120 |
FC-302P710T5 | 800 | 710 | 1460 | 1260 |
FC-302P800T5 | 1000 | 800 | 1720 | 1460 |
FC-302N90KT5 | 132 | 110 | 190 | 160 |
FC-302N110T5 | 160 | 132 | 240 | 190 |
FC-302N132T5 | 200 | 160 | 302 | 240 |
FC-302N160T5 | 250 | 200 | 361 | 302 |
FC-302N200T5 | 315 | 250 | 443 | 361 |
FC-302N250T5 | 355 | 315 | 535 | 443 |
FC-302P250T5 | 355 | 315 | 540 | 443 |
FC-302P315T5 | 400 | 355 | 590 | 540 |
FC-302P355T5 | 500 | 400 | 678 | 590 |
FC-302P400T5 | 530 | 500 | 730 | 678 |
FC-302P450T5 | 560 | 530 | 780 | 730 |
FC-302P500T5 | 630 | 560 | 890 | 780 |
FC-302P560T5 | 710 | 630 | 1050 | 890 |
FC-302P630T5 | 800 | 710 | 1160 | 1050 |
FC-302P710T5 | 1000 | 800 | 1380 | 1160 |
FC-302P800T5 | 1100 | 1000 | 1530 | 1380 |
supply voltage 525 - 600 V
Type of drive | Current, A | Power, kW |
FC-102P1K1T6… | 2,6 | 1,1 |
FC-102P1K5T6… | 2,9 | 1,5 |
FC-102P2K2T6… | 4,1 | 2,2 |
FC-102P3K0T6… | 5,2 | 3,0 |
FC-102P3K7T6… | - | 3,7 |
FC-102P4K0T6… | 6,4 | 4,0 |
FC-102P5K5T6… | 9,5 | 5,5 |
FC-102P4K0T6… | 11,5 | 7,5 |
FC-102P11KT6… | 19 | 11 |
FC-102P15KT6… | 23 | 15 |
FC-102P18KT6… | 28 | 18 |
FC-102P22KT6… | 36 | 22 |
FC-102P30KT6… | 43 | 30 |
FC-102P37KT6… | 54 | 37 |
FC-102P45KT6… | 65 | 45 |
FC-102P55KT6… | 87 | 55 |
FC-102P75KT6… | 105 | 75 |
FC-102P90KT6… | 137 | 90 |
supply voltage 525 - 690 V
Type of drive | Current, A | Motor power, kW | ||
norm. mode | heavy. mode | norm. mode | heavy. mode | |
FC-102P1K1T7… | 2,1 | - | 1,1 | - |
FC-102P1K5T7… | 2,7 | - | 1,5 | - |
FC-102P2K2T7… | 3,9 | - | 2,2 | - |
FC-102P3K0T7… | 4,9 | - | 3,0 | - |
FC-102P4K0T7… | 6,1 | - | 4,0 | - |
FC-102P5K5T7… | 9,0 | - | 5,5 | - |
FC-102P4K0T7… | 11 | - | 7,5 | - |
FC-102P11KT7… | 14 | - | 11 | - |
FC-102P15KT7… | 19 | - | 15 | - |
FC-102P18KT7… | 23 | - | 18 | - |
FC-102P22KT7… | 28 | - | 22 | - |
FC-102P30KT7… | 36 | - | 30 | - |
FC-102P37KT7… | 43 | - | 37 | - |
FC-102P45KT7… | 54 | - | 45 | - |
FC-102P55KT7… | 65 | - | 55 | - |
FC-102P75KT7… | 87 | - | 75 | - |
FC-102P90KT7… | 105 | - | 90 | - |
FC-302N55KT7 | 90 | 76 | 55 | 45 |
FC-302N75KT7 | 113 | 90 | 75 | 55 |
FC-302N90KT7 | 137 | 113 | 90 | 75 |
FC-302N110T7 | 162 | 137 | 110 | 90 |
FC-302N132T7 | 201 | 162 | 132 | 110 |
FC-302N160T7 | 253 | 201 | 160 | 132 |
FC-302N200T7 | 303 | 253 | 200 | 160 |
FC-302N250T7 | 360 | 303 | 250 | 200 |
FC-302N315T7 | 418 | 360 | 315 | 250 |
FC-302P355T7 | 470 | 395 | 355 | 300 |
FC-302P400T7 | 523 | 429 | 400 | 315 |
FC-302P500T7 | 596 | 523 | 450 | 400 |
FC-302P560T7 | 630 | 596 | 500 | 450 |
FC-302P630T7 | 763 | 659 | 560 | 500 |
FC-302P710T7 | 889 | 763 | 670 | 560 |
FC-302P800T7 | 988 | 889 | 750 | 670 |
FC-302P900T7 | 1108 | 988 | 850 | 750 |
FC-302P1M0T7 | 1317 | 1108 | 1000 | 850 |
FC-302P1M2T7 | 1479 | 1317 | 1100 | 1000 |
FC-302N55KT7 | 86 | 73 | 75 | 55 |
FC-302N75KT7 | 108 | 86 | 90 | 75 |
FC-302N90KT7 | 131 | 108 | 110 | 90 |
FC-302N110T7 | 155 | 131 | 132 | 110 |
FC-302N132T7 | 192 | 155 | 160 | 132 |
FC-302N160T7 | 242 | 192 | 200 | 160 |
FC-302N200T7 | 290 | 242 | 250 | 200 |
FC-302N250T7 | 344 | 290 | 315 | 250 |
FC-302N315T7 | 400 | 344 | 400 | 315 |
FC-302P355T7 | 450 | 380 | 450 | 355 |
FC-302P400T7 | 500 | 410 | 500 | 400 |
FC-302P500T7 | 570 | 500 | 560 | 500 |
FC-302P560T7 | 630 | 570 | 630 | 560 |
FC-302P630T7 | 730 | 630 | 710 | 630 |
FC-302P710T7 | 850 | 730 | 800 | 710 |
FC-302P800T7 | 945 | 850 | 900 | 800 |
FC-302P900T7 | 1060 | 945 | 1000 | 900 |
FC-302P1M0T7 | 1260 | 1060 | 1200 | 1000 |
FC-302P1M2T7 | 1415 | 1260 | 1400 | 1200 |
You can buy Danfoss VLT HVAC Drive FC 102 frequency converters, find out the price and more information about the products by contacting our specialists.