Regenerative converters of the series D1000 from the company Yaskawa They serve for the efficient use of consumed resources by returning excess braking energy back to the power supply network. Such a rational approach will save you money on the supply of installations and increase the environmental status of your production.
The design of the recuperative unit is very compact and takes up less space, unlike systems with braking resistors. Their use also reduces the risks associated with repair work, generally increasing reliability and stability of operation.
In addition to the block sizes listed below, a complete configuration with the code D1KIT...ABAAA is available for order, which already includes EMC filters, linear reactors and harmonic filters.
Technical characteristics of Yaskawa D1000 electric drives
- Supply voltage: 3AC 200- 240 V, 380 - 480 V ;
- Power of electric motors: 3.7 - 560 kW;
- Output current: 8 - 955 A;
- Carrier frequency: 2, 4, 6 kHz;
- Permissible overloads: heavy duty - 150% of the nom. current for 60 seconds ;
- Enclosure protection class: IP00, IP20;
- Interfaces: RS-485/RS-422 MEMOBUS/Modbus, по запросу CANopen, CC-Link, DeviceNet, EtherCAT, Ethernet/IP /Dual-Port, MECHATROLINK-II, Modbus/TCP /Dual-Port, POWERLINK, PROFIBUS-DP, PROFINET;
- Visualization and customization tools: LCD display with push-button navigation and real-time data copying function, software for control and parameterization using a personal computer ;
D1000 I/O configuration
- Digital: 8 inputs and 4 relay outputs.
- Analog: 3 inputs and 2 outputs.
Optional modules for the D1000 series
- An expansion board for analog and digital inputs/outputs.
- Modules for connecting feedback sensors (encoders, resolvers).
- Modules of industrial communication interfaces.
- USB converter for copying data and connecting a PC.
- 24 V backup power supply.
- The EMC filter.
- Mounting for carrying the control panel to the wall or cabinet door.
- Mounting for an external radiator.
Parameters of standard sizes of electric drives Yaskawa D1000
supply voltage 200 V, 3 phases
Type of drive | Power, kW | Current, A | ||
max. for the motor | nom. exit | Output (DC) | at the input (AC) | |
CIMR-DC2A0005 | 3,7 | 5 | 15 | 12 |
CIMR-DC2A0010 | 7,5 | 10 | 30 | 29 |
CIMR-DC2A0020 | 15 | 20 | 61 | 57 |
CIMR-DC2A0030 | 22 | 30 | 90 | 83 |
CIMR-DC2A0050 | 37 | 50 | 152 | 140 |
CIMR-DC2A0065 | 55 | 65 | 197 | 200 |
CIMR-DC2A0090 | 75 | 90 | 273 | 270 |
CIMR-DC2A0130 | 110 | 130 | 394 | 400 |
Supply voltage 400 V, 3 phases
Type of drive | Power, kW | Current, A | ||
max. for the motor | nom. exit | Output (DC) | at the input (AC) | |
CIMR-DC4A0005 | 3,7 | 5 | 8 | 8 |
CIMR-DC4A0010 | 7,5 | 10 | 15 | 16 |
CIMR-DC4A0020 | 15 | 20 | 30 | 30 |
CIMR-DC4A0030 | 22 | 30 | 45 | 43 |
CIMR-DC4A0050 | 37 | 50 | 61 | 58 |
CIMR-DC4A0065 | 55 | 65 | 91 | 86 |
CIMR-DC4A0090 | 75 | 90 | 152 | 145 |
CIMR-DC4A0130 | 110 | 130 | 197 | 210 |
CIMR-DC4A0185 | 160 | 185 | 280 | 300 |
CIMR-DC4A0270 | 220 | 270 | 409 | 410 |
CIMR-DC4A0370 | 315 | 370 | 561 | 560 |
CIMR-DC4A0630 | 560 | 630 | 955 | 1040 |
You can buy Yaskawa D1000 frequency converters, find out the price and more information about the products by contacting our specialists.