Main Features
| range | TeSys | |
|---|---|---|
| Product name | TeSys LF | |
| the type of device or its accessories | Direct start starter of closed design | |
| Scope of application | AS interface | |
| the composition of the device | AS Interface module The automatic switch must be ordered separately Contactor |
|
| Application category | AC-3 | |
| network type | Alternating current | |
| control circuit voltage | 24 V for alternating current circuit in 50/60 Hz | |
| range of thermal protection settings | 0.16...0.25 A | |
| type of management | Rotary handle for protection control - OFF - avar. off - ON |
Additional features
| network frequency | 50/60 Hz | |
|---|---|---|
| [Ue] rated operating voltage | 415 V - Alternating current at 50/60 Hz for power circuit- 250 V - Alternating current at 50/60 Hz for relay control output 30 V - Direct current for relay control output |
|
| [Up] rated pulse withstand voltage | 6 kV for power circuit according to IEC 60947-1 2.5 kV for 24 V in accordance with IEC 60947-1 2.5kV for sensor according to IEC 60947-1 2.5 kV for AS-Interface according to IEC 60947-1 |
|
| insulation resistance | > 1000 mOhm between output and data transmission | |
| isolation | 1500 V between outlet and ground 1500 V between output and internal logic Between the entrance and the communication line |
|
| [Ui] rated insulation voltage | AC at 50/60 Hz conforming to IEC 60947 | |
| [Ithe] conditional thermal current in a closed case | 5 A for relay control output at 40 °C | |
| types of implemented protections | Inductive overvoltage Phase breakage |
|
| breaking capacity | 100 kA at 230/240 V in accordance with IEC 60947-2 100 kA at 400/415 V in accordance with IEC 60947-2 |
|
| mechanical wear resistance | Circuit breaker : 0.1 million cycles Contactor : 30 million cycles |
|
| electrical wear resistance | Circuit breaker : 0.1 million cycles Contactor : 0.8 million cycles - AC-3 - 8.5 A Relay : 0.1 million cycles - 24 V with 6 cycles/m - AC-12 - 5 A Relay : 1 million cycles - 24 V with 15 CYC/MN - AC-12 - 1 A Relay : 0.5 million cycles - 24 V with 15 CYC/MN - AC-14 - 1 A Реле : 1 млн. циклов - 24 В с 15 cyc/mn - AC-14 - 0.5 A Relay : 5 Mcycles - 24 V with 30 cycle/m - AC-14 - 0.25A Relay : 0.1 million cycles - 24 V with 6 cycles/m - DC-12 - 5 A Relay : 0.2 million cycles - 24 V with 6 cycles/m - DC-12 - 2 A Relay : 0.5 million cycles - 24 V with 15 CYC/MN - DC-3 - 1 A Relay : >=1 Mcycles - 24 V with 30 cycle/m - DC-3 - 0.25A |
|
| current consumption | 20 mA for communication bus during operation 60 mA for communication bus sensor 0 mA to 24 V for power supply circuit voltage relief 30 mA to 24 V for the power supply circuit is supported. mode 110mA to 24V for power supply circuit throw |
|
| local indication | Product status via 3 LEDs The status of the I/O. by means of an LED |
|
| number of inputs | 2 M12 | |
| Input voltage | 19...30 V 50 mA - direct current | |
| description of the entrance | Status D0 : stop forward - bit value 0 Status D1 : stop back - bit value 0 Status D2 : relay shutdown - bit value 0 D3 status : not used - bit value 0 Status D0 : start forward - value of bit 1 Status D1 : start back - value of bit 1 Status D2 : switching on the relay - the value of bit 1 D3 status : not used - bit value 1 |
|
| type of entry | Resistive | |
| Input compatibility | 2- or 3-wire PNP | |
| description of the output | Command D0 : not ready - bit value 0 Command D1 : stopped - bit value 0 Command D2 : sensor 1 no signal - bit value 0 Command D3 : sensor 2 no signal - bit value 0 Command D0 : ready - value of bit 1 Command D1 : started - value of bit 1 Command D2 : sensor 1 signal presence - bit value 1 Command D3 : sensor 2 signal presence - bit value 1 |
|
| the time when the command was executed by the switch | Relay control output : <= 10 ms в течение включение Relay control output : ≤ 15 ms during shutdown |
|
| type of contacts | 1 Switching. | |
| ??????? AS-Interface | 7DFF - standard | |
| type of cable gland | Power supply chain : Pg 16 - 10...15 mm Power circuit- : Pg 16 - 10...15 mm Relay control output : Pg 13 - 10...15 mm Relay control output : Pg 16 - 10...15 mm |
|
| accessions | Power supply chain: screw clamp 1 x 1.5...2 x 6 mm2 hard Power supply chain: screw clamp 1 x 1.5...2 x 6 mm2 flexible without tip Power supply chain: screw clamp 1 x 1.5...2 x 4 mm2 flexible with cable tip Power chain: screw clamp 1 x 1.5...2 x 4 mm2 rigid Power chain: screw clamp 1 x 1.5...2 x 4 mm2 flexible without tip Power chain: screw clamp 1 x 1.5...1 x 2.5 mm2 flexible with cable tip Relay control output: screw terminals 1 x 0.5...1 x 1.5 mm2 hard Relay control output: screw terminals 1 x 0.5...1 x 1.5 mm2 flexible without tip Relay control output: screw terminals 1 x 0.5...1 x 1.5 mm2 flexible with cable tip |
|
| tightening torque | Power supply chain : 1.7 N-m - with a screwdriver Ø 5.5 mm Power circuit : 0.8 N-m - with a screwdriver Ø 5.5 mm Relay control output : 0.7 N-m - using a screwdriver flat. Ø 3.5 mm |
|
| width | 175 mm | |
| height | 195 mm | |
| depth | 175 mm | |
| Product weight | 1.02 kg |
Operating conditions
| electromagnetic compatibility | Electrostatic discharge 8 kV level 3 - in air - in accordance with EN/IEC 61000-4-2 Electrostatic discharge 4 kV level 2 - with indirect contact - in accordance with EN/IEC 61000-4-2 Immunity test for switching interference/short packets 2 kV level 3 in accordance with EN/IEC 61000-4-4 4 kV pulse interference immunity test level 4 - power supply, phase voltage - in accordance with IEC 61000-4-5 Pulse immunity test 2 kV level 4 - power supply, line voltage - in accordance with EN/IEC 61000-4-5 Pulse immunity test 2 kV level 2 - control circuit, phase voltage - in accordance with IEC 61000-4-5 Pulse immunity test 500 V level 2 - control circuit, line voltage - in accordance with EN/IEC 61000-4-5 Induced RF interference of 10 V/m in accordance with IEC 61000-4-6 Induced RF interference of 10 V/m in accordance with ENV 50141 10 V/m RF interference resistance test according to IEC 61000-4-3 10 V/m RF interference resistance test according to ENV 50204 10 V/m RF interference resistance test according to ENV 50140 Radiated electromagnetic field class B according to ENV 55011 Radiated electromagnetic field class B according to CISPR 11 |
|
|---|---|---|
| mechanical resistance | Shocks : 10 Gn during contactor open according to IEC 60068-2-27 Shocks : 15 gn during contactor is closed according to IEC 60068-2-27 Vibration : 2 Gn during contactor open according to IEC 60068-2-6 Vibration : 4 gn during contactor closed according to IEC 60068-2-6 |
|
| degree of IP protection | IP54 in accordance with IEC 60529 | |
| protective design | TC | |
| Fire resistance | 960 °C in accordance with IEC 60695-2-1 | |
| working height | 2000 m | |
| standards | EN 60204-1 EN 60439-1 EN 60947-1 IEC 60204-1 IEC 60439-1 IEC 60947-1 |
|
| material | Bottom : Polycarbonate + 20 % FG - black Upper : polycarbonate + 20 % FG - white : RAL 9001 |
|
| Ambient operating temperature | -5...40 °C in accordance with IEC 61439-1 | |
| ambient temperature during storage | -40...80 °C in accordance with IEC 61439-1 |