Information about the pressure regulator "after itself" RA-A 50-25-1-SCH-1,6-150- U
Direct-acting pressure regulators of the 100 series, RA-M - pressure drop, RA-A - “after itself”, RA-B - “before itself” PN 1.6 MPa
Y is the setting range, MPa:
- 0,04-0,16
- 0,1-0,4
- 0,3-0,7
- 0,6-1,2
XXX - Kvy throughput, m3/h
Appointment
The regulator is designed for installation in heating and water supply systems for cold and hot water or a 30% aqueous solution of ethylene glycol with a temperature of no more than 150 ° C and a pressure of no more than 1.6 MPa.
Materials used
Detail |
Material |
Body |
Cast iron SCH 20 |
Plunger, Saddle, stem |
Steel 20X13 |
Membrane box |
CAM35 |
The membrane |
EPDM |
Spring |
60X2A |
Stem seal |
Fluoroplast |
Technical specifications
Name of the parameter |
Meaning |
||||||||
Nominal diameter DN |
25 |
32 |
40 |
50 |
65 |
80 |
100 |
125 |
150 |
Conditional throughput, Kvy, m3 /h |
1,6 2,5 4,0 6,3 10 |
6,3 10 16 |
10 16 25 |
10 16 25 32 40 |
25 32 40 63 |
40 63 100 |
63 100 160 |
100 125 160 250 |
160 250 360 |
Nominal pressure PN, MPa, no more |
1,6 |
||||||||
Working environment temperature, aboutWith |
-15... + 150 |
||||||||
No. of the adjustment range of the regulator (Mpa) |
|
1 (0,04.0,16) 2 (0,1 .0,4) 3 (0,3...0,7) 4 (0,6. 1,2) |
|
||||||
The proportionality zone, % |
no more than 6 |
||||||||
The zone of insensitivity, % |
no more than 1.6 |
||||||||
Time constant, sec |
no more than 6 |
||||||||
Relative leakage, % of Kvy |
not more than 0.05 |
||||||||
Connection to the pipeline |
Flanged with connection dimensions according to GOST 12815-80 |
Mounting sets of regulators
Designation the regulator |
Designation The kit |
The composition of the kit |
Quantity |
|
|
Adapter G1/2" x G1/4>> |
2 |
|
|
Mortise ring |
4 |
The regulator |
|
Tightening nut |
4 |
the difference |
MK-1.1 |
Pads |
4 |
pressure |
Housing G1/4>> |
2 |
|
(RA-M) |
|
Housing M12 x1.5 |
2 |
|
|
Copper tube |
1.5; 0.75 m |
|
|
Pressure gauge |
2 |
Pressure regulator "after itself" |
|
Adapter G1/2" x G1/4>> |
1 |
|
Mortise ring |
3 |
|
|
Tightening nut |
3 |
|
|
Pads |
3 |
|
|
MK-2.1 |
Housing G1/4>> |
1 |
Pressure regulator "up to itself" |
|
Housing M12 x1.5 |
2 |
|
Plug |
1 |
|
|
Copper tube |
1.5; 0.3 m |
|
|
Pressure gauge |
1 |
Overall dimensions
Parameter |
Nominal diameter DN |
||||
25 |
32 |
40 |
50 |
65 |
|
L, mm |
160 |
180 |
200 |
230 |
290 |
H, mm, no more |
620 |
640 |
655 |
670 |
705 |
H1, mm, no more |
575 |
595 |
600 |
610 |
625 |
Weight, kg, no more |
14 |
18 |
20 |
22 |
32 |
Parameter |
Nominal diameter DN |
|||
80 |
100 |
125 |
150 |
|
L, mm |
310 |
350 |
400 |
480 |
H, mm, no more |
720 |
760 |
800 |
880 |
H1, mm, no more |
630 |
660 |
690 |
740 |
Mass, kg, no more |
38 |
45 |
50 |
60 |