Description
Features
Reviews
Main Features
range | TeSys | |
---|---|---|
Product name | TeSys T | |
short name of the device | LTMR | |
the type of device or its accessories | Electric motor controller | |
Scope of application | Control and monitoring of equipment | |
Measurement current | 1.35...27 A | |
[Us] rated mains voltage | 24 V DC | |
current consumption | 56...127 mA | |
supply voltage limits | 20.4...26.24 V DC | |
data exchange port protocol | Modbus | |
type of tire | Modbus 2-wire RS 485 interface, address 1...247, transmission rate 1.2...19.2 Kbit/s, RJ45 with 2 shielded twisted pairs Modbus 2-wire RS 485 interface, access 1...247, transmission rate 1.2...19.2 Kbit/s, terminal block with 2 shielded twisted pairs |
Additional features
[Ui] rated insulation voltage | 690 V in accordance with CSA C22.2 No. 14 690 V in accordance with EN/IEC 60947-1 690 V in accordance with UL 508 |
|
---|---|---|
[Up] rated pulse withstand voltage | 6 kV for current or voltage measurement circuit according to EN/IEC 60947-4-1 0.8 kV for data exchange circuit according to EN/IEC 60947-4-1 0.8kV for power supply, inputs and outputs in accordance with EN/IEC 60947-4-1 |
|
sustained short circuit | 100 kA in accordance with EN/IEC 60947-4-1 | |
the corresponding fuse rating | 0.5A gG for control circuit 4 A gG for output |
|
types of implemented protections | Current leakage protection Phase breakage Protection against switching on with reverse polarity Thermal overload protection Thermal protection Reboot Phase imbalance Fixed rotor Overload (long time) Load fluctuation Changing the power factor |
|
types of checks and diagnostics of the device | Phase fault and ground fault counters Remaining operating time before overload shutdown Working hours counter Inrush current and time Waiting time after overvoltage shutdown Fault recording Recording of meetings Contextual information History data Recording of engine control commands |
|
the number of the logical input | 6 | |
Input current | 7 mA | |
current state 0 guaranteed | Digital input : < 5 В и <= 15 mA для 5 ms | |
current state 1 guaranteed | Digital input : < 15 V и 2...15 mA для 15 ms | |
maximum switching frequency | 2 Hz | |
Load current | 5 A to 250 V AC for logic output 5 A to 30 V DC for logic output |
|
Permissible power | 480 VA (AC-15), Ie=2A, 500000 cycles (output) 30 W (DC-13), Ie=1.25 A, 500000 cycles (output) |
|
Operating frequency | 1800 cycle/h | |
type of contacts | 1 N.O. + 1 N.Z. alarm 3 N.O. |
|
measured parameters | Short circuit to earth Phase current I1, I2, I3 RMS Temperature Average current Current imbalance |
|
Measurement accuracy | 3 % power factor (cos φ >0.6) +/- 30 min./year built-in clock 0.02 temperature 5...15 % measurement of ground fault current by built-in TT (for current >0.2 A) 1 % current 1 % voltage (100...830 V) 5 % active and reactive power 5 % measurement of ground fault current by external TT (< 5 % или 0,01 A) |
|
Overvoltage category | III | |
connection step | 5.08 mm | |
accessions | Connector, 1 flexible cable with a 0.25 cable tip...2.5 mm2 /AWG 24...AWG 14 for control circuit Connector, 1 flexible cable without cable tip 0.2...2.5 mm2 /AWG 24...AWG 14 for control circuit Connector, 1 flexible cable without cable tip 0.25...2.5 mm2 /AWG 24...AWG 14 for control circuit Connector, 1 hard cable Cable without cable tip 0.2...2.5mm2 /AWG 24...AWG 14 for control circuit Connector, 2 flexible cables with cable tip 0.2...1 mm2 /AWG 24...AWG 14 for control circuit Connector, 2 flexible cables without cable tip 0.2...1.5 mm2 /AWG 24...AWG 14 for control circuit Connector, 2 flexible cables without cable tip 0.5...1.5 mm2 /AWG 24...AWG 14 for control circuit Connector, 2 hard cable Cable without cable tip 0.2...1 mm2 /AWG 24...AWG 14 for control circuit |
|
tightening torque | 0.5...0.6N-m, 3mm Flat screwdriver for Control circuit | |
degree of contamination | 3 | |
electromagnetic compatibility | ● Electrostatic discharge 3 (8 kV through air; 6 kV on contact), in accordance with EN/IEC 61000-4-2 ● test for resistance to switching interference other circuits level 3 (2 kV), in accordance with EN/IEC 61000-4-4 ● test for resistance to switching interference in power supply circuits and relay outputs level 4 (4 kV), in accordance with EN/IEC 61000-4-4 ● Induced RF interference (10 V), in accordance with EN/IEC 61000-4-6 ● Pulse interference general mode (1 kV) control circuit, in accordance with EN/IEC 61000-4-5 ● Pulse interference in serial mode (1 kV) control circuit, in accordance with EN/IEC 61000-4-5 ● Pulse interference general mode (2 kV) data exchange, in accordance with EN/IEC 61000-4-5 ● Radiated RF fields 3 (10 V/m), in accordance with EN/IEC 61000-4-3 ● test for resistance to failures and short-term voltage losses (70%, 500 ms), in accordance with EN/IEC 61000-4-11 ● Pulse interference serial mode (0.5kV) temperature sensor, according to EN/IEC 61000-4-5 ● Pulse interference general mode (1 kV) temperature sensor, in accordance with EN/IEC 61000-4-5 ● Pulse interference in serial mode (2 kV) relay outputs and power supply circuits, in accordance with EN/IEC 61000-4-5 ● Pulse interference general mode (4 kV) relay outputs and power supply circuits, in accordance with EN/IEC 61000-4-5 |
|
width | 91 mm | |
height | 61 mm | |
depth | 122.5 mm | |
Product weight | 0.53 kg | |
web services | Web server | |
compatibility code | LTMR |
Operating conditions
standards | EN 60947-4-1 IACS E10 IEC 60947-4-1 UL 508 CSA C22.2 № 14 |
|
---|---|---|
Product certification | ABS ATEX BV CCC CSA C-Tick DNV GL Reverse LROS (Lloyds register of shipping) NAME RINA RMRoS br>EAC |
|
protective design | 12 x 24 h cycles according to EN/IEC 60068-2-30 48 h according to EN/IEC 60070-2-11 TH in accordance with EN/IEC 60068 |
|
Fire resistance | 650 °C in accordance with EN/IEC 60695-2-12 960 °C in accordance with UL 94 |
|
Ambient operating temperature | -20...60 °C | |
ambient temperature during storage | -40...80 °C | |
working height | <= 2000 м без ухудшение характеристик | |
mechanical resistance | ● Shocks are half the acceleration of a sine wave (15 g (nom.) for 11 ms) in accordance with EN/IEC 60068-2-27 ● Vibration is mounted on a symmetrical rail (1 Gn, 5...300 Hz) in accordance with EN/IEC 60068-2-6 ● Vibration mounted on the board (4 g (nom.), 5...300 Hz) in accordance with EN/IEC 60068-2-6 |
|
degree of IP protection | IP20 |