Write to
WhatsApp
Catalog

TKD Kabel NYY-J 0.6/1 kV NYY-O 0.6/1 kV Power Cables

For comparison
To favorites
Vendor code:200020840
TKD Kabel NYY-J 0.6/1 kV NYY-O 0.6/1 kV Power Cables
Brand
Pre-order
$19.04
11
Delivery across Russia
On-line payment on the website
Discount system
Purchase returns
Description
Features
Reviews

Power cable NYY-J 0.6-1 kV; NYY-O 0.6-1 kV manufactured by TKD kabel (TKD cable) is used for power plants, for distribution and industrial devices, for local networks. It is used for indoor installation, as well as outside, in soil, in cable ducts and in water.

Technical specifications:

Number of conductive cores: up to 61; Core diameter: up to 500mm2;

Conductor: copper;

Structure: according to From CEOE 0295 category 1 or 2, corresponds to IEU 60228 category 1 or 2;

Insulation Material: PVX;

Marking of veins: NYY-J for a single -core cable - green - yellow, stranded according to CEOE 0207 part 5, up to 5 veins - according to CEOE 0293 - 308; NYY-O for a single-core cable - black, stranded according to CEOE 0207 part 5, without the green - yellow vein;

Twisting method: layer-by-layer concentric winding;

Internal insulation: filler;

The outer shell of the cables NYY-J 0,6/1 kV; NYY-O 0,6/1 kV: PVX;

The minimum bending radius is static: single-core cable - 15 x cable thickness; stranded - 12 x cable thickness;

Travel temperature: - 5 C /+ 50 S;

Static temperature: -40 C /+70 C;

The maximum temperature on the conductor: +70 C - in operation; +160 - in case of short circuit;

Shell characteristics: according to From CEOE 0472 part 804, type of tests In and IEU 60332 – 1;

Standard: according to From CEOE 0271 and IEFrom 60502;

Norms: CEOE.

 

Environmental requirements:

The outer shell is resistant to UV radiation.

When laying the cable NYCWY 0,6/1 kV in dry rooms, end couplings are not required.

Organosilicon rubber is not used (in the manufacture).

Features