Write to
WhatsApp
Catalog

Выключатель автоматический 100А 25кА NSX100B MICROLOGIC5.2A4П4Т электронный расцепитель (LV429875)

For comparison
To favorites
Vendor code:LV429875
-100%
Выключатель автоматический 100А 25кА NSX100B MICROLOGIC5.2A4П4Т электронный расцепитель (LV429875)
Brand
Pre-order
$0$8.74
11
Related files
Delivery across Russia
On-line payment on the website
Discount system
Purchase returns
Description
Features
Reviews

Main Features

range Compact
Product name Compact NSX
the type of device or its accessories Automatic switch
short name of the device Compact NSX100B
Scope of application Distribution
description of the poles 4P
description of the protected poles 3t
3t + 1.6 N
3t + N/2
4t
neutral position Leftward
network type Alternating current
network frequency 50/60 Hz
[In] rated current 100 A ( 40 °C )
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Up] rated pulse withstand voltage 8 kV
[Ue] rated operating voltage 690 V alternating current 50/60 Hz
breaking capacity code B (25 kA) alternating current
breaking capacity 25 kA Icu at 380/415 V AC 50/60 Hz according to IEC 60947-2
15 kA Icu in 500 V AC 50/60 Hz according to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz according to IEC 60947-2
40 kA Icu in 220/240 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated operating breaking capacity ICS 20 kA 440 V alternating current 50/60 Hz in accordance with IEC 60947-2
ICS 25 kA 380/415 V AC 50/60 Hz according to IEC 60947-2
ICS 40 kA 220/240 V AC 50/60 Hz according to IEC 60947-2
ICS 7.5 kA 500 V alternating current 50/60 Hz in accordance with IEC 60947-2
compliance with insulation requirements Yes according to EN 60947-2
Yes in accordance with IEC 60947-2
Application category Category A
name of the control unit Micrologic 5.2 A
technology of the control and management unit Electronic
protective functions of the control unit LSI
rated current of the decoupler 100 A ( 40 °C )
types of implemented protections Instant short circuit protection
Overload protection (with long time delay)
Short circuit protection with short time delay
degree of contamination 3 in accordance with IEC 60664-1

Additional features

management method Toggle switch
switch design Stationary
mounting support Rear mounting plate
connection from the upper side The front one
connection from the bottom side The front one
mechanical wear resistance 50000 cycles
electrical wear resistance 10000 cycles of 690 V In according to IEC 60947-2
20000 cycles 690 V In/2 in accordance with IEC 60947-2
30000 cycles 440 V In according to IEC 60947-2
50000 cycles of 440 V In/2 in accordance with IEC 60947-2
connection step 35 mm
local indication LED "105 % Ir"
LED "90% Ir"
The LED is "ready to work"
neutral protection setpoint 0,5 x Ir 3t + N/2
1 x Ir 4t
1,6 x Ir 3t + OSN
No 3t protection
protection setpoint with a long delay in the operation of the Ir Adjustable
[Ir] overload protection trip current setpoint 40...100 A
the type of adjustment of the overload response time delay Adjustable.
[tr] adjustable overload protection time setting 15...400 with 1.5 x Ir
0.35...11 with 7.2 x Ir
0.5...16 with 6 x Ir
thermal memory 20 minutes before and after activation
Isd short circuit protection setpoint range Adjustable.
[Isd] short circuit actuation current setpoint 1.5...10 x Ir
type of short circuit protection response time setting Adjustable
[tsd] short circuit response time adjustment range 0...0.4 s
The range of instantaneous protection settings of type Ii Adjustable
the setpoint of the instantaneous response current 1,5...15 x In
logical selectivity of ZCI With
data exchange Current and power consumption
Energy calculation
Instantaneous values and consumption values
Indicators of the need for maintenance
Display min./max. values
Power supply quality
Protection and alarm settings
Logs and tables of events with timestamps
display type LCD display
type of measurements Ammeter
stored electrical parameters Indicators of the need for maintenance
height 161 mm
width 140 mm
depth 86 mm
Product weight 2.4 kg

Operating conditions

Overvoltage category Class II
protection class against electric shock Class II
standards EN/IEC 60947
Product certification CCC
Marine version
EAC
degree of IP protection IP40 in accordance with IEC 60529
degree of protection IK IK07 in accordance with IEC 62262
Ambient operating temperature -35...70 °C
ambient temperature during storage -55...85 °C

Features
Brand
No reviews yet — yours could be the first.
All reviews 0
overall rating