Cable H05SS-F /H05SS-F EWKF productions TKD kabel (TKD cable) it has a temperature class H with an upper limit of permissible values +180 ° C It is used for connecting and monitoring electrical equipment. It is suitable for stationary use and laying movably, but without forced actions and stretching.
Cable materials do not ignite in fire, are resistant to ozone, ultraviolet radiation, and acids. It is resistant to seawater, in general, to hydrolysis processes. It is recommended for indoor and outdoor installation (except for underground installation), all-weather.
The model has two types of execution: standard and reinforced (in relation to cuts, tears, abrasion, notches).
Technical characteristics of heat-resistant cable H05SS-F /H05SS-F EWKF:
Number of conductive cores: up to 5;Core cross-section: up to 6 mm2
Conductor: tinned copper, multi-wire;
Configuration: Class 5, according to DIN VDE 0295 and IEC 60228;
Core marking: colored, DIN VDE 0293-308 coding;
Twisting: twisting in layers;
Insulation material: Silicone /extra durable silicone EWKF;
Outer shell: silicone /extra durable EWKF silicone;
Operating voltage: 0.3 - 0.5 kV;
Test voltage: 2 kV;
Conductor resistance: Class 5, according to DIN VDE 0295 and IEC 60228;
Insulation resistance: minimum 2 GOm;
Minimum bending radius (stationary):4 x Diameter;
Minimum bending radius (movable):15 x Diameter;
Temperature (stationary): -50 ° C /+180 ° C;
Insulation material properties: non-flammable from fire, VDE 0482-332-2-1 (IEC 60332-1);
Environmental requirements: all-weather, resistant to UV radiation, ozone and hydrolysis (including from seawater).