Detector IP101-07w 1Exd[ia]IICT4/T5/T6 X

For comparison
To favorites
Vendor code:ИП101-07вт
Detector IP101-07w 1Exd[ia]IICT4/T5/T6 X
Brand
Pre-order
$112.22
11
Delivery across EC anв UAE
On-line payment on the website
Discount system
Purchase returns
Description
Features
Reviews

Detector IP101-07w 1Exd[ia]IICT4/T5/T6 X


Distinctive features:
- connection for both circuit opening and short circuit
- connection to address fire alarm systems
- the standard length of the sensor element is 1.5 meters, the maximum length is up to 30 meters (on request)

Construction:
- available in an aluminum alloy housing AK 12 IF
- non-oxidizing WAGO spring terminals
- the sensing element is made of stainless steel
- the detector housing with electronic components is spatially separated from the sensor element, which allows you to control the heating zone up to 250 °C

Key Features:
- unique thermal sensitivity
- light indication when triggered
- high dust and moisture resistance IP67 and vibration resistance (compound filling)
- separate marking of the explosion protection of the housing and the sensor element


Specifications:
- marking of the explosion protection of the housing 1Exd[ia]IICT4/T5/T6 X
- marking of the explosion protection of the sensor element 0ExiaIIST2/T3/T4/T5/T6 X
- detector temperature setting class A1, A2, A3, B, C, D, E, F, G, H
- operating temperature, °C 54-250
- supply voltage, 8-28 V
- maximum current consumption, 200 Ma
Operating conditions:
- ambient temperature for the corresponding temperature classes, °C
for the remote element
T2 - from - 60 to + 250
T3 - from - 60 to + 200
T4 - from - 60 to + 135
T5 - from - 60 to + 100
for the detector housing
T6 - from - 60 to + 85
- overall dimensions, not more than 200x94x60 mm
- weight, not more than 1.0 kg
TU 4371-008-43082497-05-01

The setting temperature of the explosion-proof detector is specified by the consumer upon request. If a temperature class is specified, the detector is adjusted to the temperature corresponding to the middle of the class, according to the table below.

Class A1 Setting temperature,°C 60 Temperature*,°C 54-65
Class A2 Setting temperature,°C 60 Temperature*,°C 54-70
Class A3 Setting temperature,°C 70 Temperature*,°C 64-76
Class B Setting temperature,°C 75 Temperature*,°C 69-85
Class C Setting temperature,°C 90 Temperature*,°C 84-100
Class D Setting temperature,°C 105 Temperature*,°C 99-115
Class E Setting temperature,°C 120 Temperature*,°C 114-130
Class F Setting temperature,°C 135 Temperature*,°C 129-145
Class G Setting temperature,°C 150 Temperature*,°C 144-160
Class H Setting temperature,°C on request Temperature*,°C 159-200

Class H Setting temperature,°C on request Temperature*,°C 200-250


Features
Brand
No reviews yet — yours could be the first.
All reviews 0
overall rating
Similar products
Hit
Ultrasonic level meter FMU41-ARB3A2
Ultrasonic level meter FMU41-ARB3A2
$1,411.83
In stock
Discount
Encoder ECN1023 S512 ID: 1211019-01
Encoder ECN1023 S512 ID: 1211019-01
$1,164.76
In stock
Speck Pumpen V Vacuum Pumps
Speck Pumpen V Vacuum Pumps
$20.59
Pre-order
Hit
Baumer Huebner GTB9.06L/420 K1 tachogenerator
Hit
Pneumatic hammer 03607000 PKL 740/6
Pneumatic hammer 03607000 PKL 740/6
$926.52
Still have 1 qty
Asynchronous servomotors KEB DM /DA
Asynchronous servomotors KEB DM /DA
$20.59
Pre-order
Список отзывов пуст